Methods can change from story to story and line to line; mixing on one line is allowed in SDC A-B (and detached C) if the line uses the most demanding method's length.
Restraints resist a sideways force of one-third the operating weight; floor units strap in their top third and hung units brace 4 ways (flexible) or 2 ways (rigid).
Relief discharge pipe: full size, gravity-drained, untrapped, one valve only, not tied to the drain, ending visibly within 6 in of the floor or receptor in the same room, unthreaded, with no valves or tees.
Kitchen exhaust ducts outdoors through a smooth, airtight, dedicated duct with a backdraft damper, never into an attic, crawl space or indoors; listed ductless hoods are allowed where other ventilation exists.
Searches all 4,276 IRC 2024 sections, 5,532 IBC 2024 sections and defined terms (Chapters 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16, 17, 18, 19, 20, 21, 22, 23, 24, 25, 26, 27, 28, 29, 30, 31, 32, 33 so far) and each city's local rules as they are added. Section numbers and titles from the International Residential Code and International Building Code, 2024 editions, copyrighted by the International Code Council; the IRC's electrical chapters (34 to 43) follow NFPA 70, the National Electrical Code. Requirements are summarized in our words (IRC Chapters 3 to 43, IBC Chapters 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16, 17, 18, 19, 20, 21, 22, 23, 24, 25, 26, 27, 28, 29, 30, 31, 32, 33); read the full text at the link on each result. Local values come from each city's published documents.