Rods, pipes and plates go below the permanent moisture level where practical, free of paint, and 6 ft from another system's electrodes; their sole jumper needn't exceed 6 Cu / 4 Al (NEC 250.53).
Working space is kept around electrical equipment; open doors may not shrink access below 24 in wide and 6.5 ft high; no foreign equipment in the zone 6 ft above panels, no storage, lit indoors (NEC 110.26).
Strip vegetation, topsoil and debris inside the foundation; clean fill is compacted and limited to 24 in of sand or gravel or 8 in of earth unless approved.
Searches all 4,276 IRC 2024 sections, 5,532 IBC 2024 sections and defined terms (Chapters 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16, 17, 18, 19, 20, 21, 22, 23, 24, 25, 26, 27, 28, 29, 30, 31, 32, 33 so far) and each city's local rules as they are added. Section numbers and titles from the International Residential Code and International Building Code, 2024 editions, copyrighted by the International Code Council; the IRC's electrical chapters (34 to 43) follow NFPA 70, the National Electrical Code. Requirements are summarized in our words (IRC Chapters 3 to 43, IBC Chapters 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16, 17, 18, 19, 20, 21, 22, 23, 24, 25, 26, 27, 28, 29, 30, 31, 32, 33); read the full text at the link on each result. Local values come from each city's published documents.