Gas cooktops need 30 in to combustibles and metal cabinets above, or 24 in with millboard and sheet metal protection, a 28-gauge hood 1/4 in below, or a listed over-range appliance.
NM cable sheath enters the box at least 1/4 in and is secured, except in single-gang boxes no larger than 2 1/4 x 4 in where the cable is stapled within 8 in (NEC 314.17(B)(2)).
Closet storage space runs 24 in from walls up to 6 ft (or the top rod), then 12 in or shelf width above; only enclosed or fluorescent fixtures, with 12 in clearance for surface incandescent/LED and 6 in for fluorescent and recessed (NEC 410.16).
Searches all 4,276 IRC 2024 sections, 5,532 IBC 2024 sections and defined terms (Chapters 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16, 17, 18, 19, 20, 21, 22, 23, 24, 25, 26, 27, 28, 29, 30, 31, 32, 33 so far) and each city's local rules as they are added. Section numbers and titles from the International Residential Code and International Building Code, 2024 editions, copyrighted by the International Code Council; the IRC's electrical chapters (34 to 43) follow NFPA 70, the National Electrical Code. Requirements are summarized in our words (IRC Chapters 3 to 43, IBC Chapters 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16, 17, 18, 19, 20, 21, 22, 23, 24, 25, 26, 27, 28, 29, 30, 31, 32, 33); read the full text at the link on each result. Local values come from each city's published documents.