  • IBC 716.1

    General

    • Opening protectives follow this section and NFPA 80.
    • Door rating by wall rating: 4-hour wall 3-hour door; 3-hour 3-hour; 2-hour 1½-hour; 1½-hour 1½-hour; 1-hour shaft and exit enclosures 1-hour; other 1-hour barriers ¾-hour; 1-hour corridor walls 20 minutes; other 1-hour partitions ¾-hour; ½-hour partitions 20 minutes; smoke barriers 20 minutes; exterior 2-hour walls 1½-hour, 1-hour walls ¾-hour.

    International Building Code, 2024 · Chapter 7, Fire and Smoke Protection FeaturesRead the full text (opens UpCodes in a new tab)

  • IBC 716.1.1

    Alternative methods for determining fire protection ratings

    • Ratings may come from approved designs, engineering comparison or 104.2.3 alternatives.

    Works withIBC 104.2.3

    International Building Code, 2024 · Chapter 7, Fire and Smoke Protection FeaturesRead the full text (opens UpCodes in a new tab)

  • IBC 716.1.2.1

    Safety glazing

    • Fire-rated glazing also meets Chapter 24 safety glazing.

    Works withIBC Chapter 24

    International Building Code, 2024 · Chapter 7, Fire and Smoke Protection FeaturesRead the full text (opens UpCodes in a new tab)

  • IBC 716.1.2.3

    Fire-resistance-rated glazing

    • E119-tested glazing in a rated wall or floor needn't otherwise meet this section.

    International Building Code, 2024 · Chapter 7, Fire and Smoke Protection FeaturesRead the full text (opens UpCodes in a new tab)

  • IBC 716.1.2.2.1

    Fire-rated glazing identification

    • D = door use, H = hose stream, T = temperature rise, XXX = minutes.

    International Building Code, 2024 · Chapter 7, Fire and Smoke Protection FeaturesRead the full text (opens UpCodes in a new tab)

  • IBC 716.1.2.2.4

    Fire-rated glazing that exceeds the code requirements

    • Glazing rated higher or with extra H or T markings may be used where less is required.

    International Building Code, 2024 · Chapter 7, Fire and Smoke Protection FeaturesRead the full text (opens UpCodes in a new tab)

  • IBC 716.1.2.3.1

    Glazing in fire door and fire window assemblies

    • Fire-resistance glazing is allowed in fire doors and windows per listing.

    International Building Code, 2024 · Chapter 7, Fire and Smoke Protection FeaturesRead the full text (opens UpCodes in a new tab)

  • IBC 716.3.2

    Performance requirements

    • Fire windows meet Table 716.1(3): ¾-hour in 1-hour partitions, barriers and smoke barriers; 20 minutes in ½-hour partitions; 1½-hour in exterior walls over 1 hour; not allowed in fire walls or barriers over 1 hour unless E119-tested.

    International Building Code, 2024 · Chapter 7, Fire and Smoke Protection FeaturesRead the full text (opens UpCodes in a new tab)

Searches all 4,276 IRC 2024 sections, 5,532 IBC 2024 sections and defined terms (Chapters 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16, 17, 18, 19, 20, 21, 22, 23, 24, 25, 26, 27, 28, 29, 30, 31, 32, 33 so far) and each city's local rules as they are added. Section numbers and titles from the International Residential Code and International Building Code, 2024 editions, copyrighted by the International Code Council; the IRC's electrical chapters (34 to 43) follow NFPA 70, the National Electrical Code. Requirements are summarized in our words (IRC Chapters 3 to 43, IBC Chapters 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16, 17, 18, 19, 20, 21, 22, 23, 24, 25, 26, 27, 28, 29, 30, 31, 32, 33); read the full text at the link on each result. Local values come from each city's published documents.