Every 2024 IRC section and the IBC as it loads, by number or topic, plus the local rules for your city. Free to search.
All Permits & administration Building Energy Mechanical & gas Plumbing Electrical San Antonio rules
35 sections matching “IBC 414” for San Antonio, TX, the 2024 IRC IBC 414.1
IBC 414.2
IBC 414.3
Ventilation Spaces that may emit hazardous dusts, mists, fumes or gases are mechanically ventilated as required. Works with IFC IMC
International Building Code, 2024 · Chapter 4, Special Detailed Requirements Based on Occupancy and Use Read the full text (opens UpCodes in a new tab)
IBC 414.4
Hazardous material systems Systems suit their use, control material flow and fail safe. International Building Code, 2024 · Chapter 4, Special Detailed Requirements Based on Occupancy and Use Read the full text (opens UpCodes in a new tab)
IBC 414.5
Inside storage, dispensing and use Indoor storage and use follows 414.5.1 to 414.5.3 and the IFC. International Building Code, 2024 · Chapter 4, Special Detailed Requirements Based on Occupancy and Use Read the full text (opens UpCodes in a new tab)
IBC 414.6
IBC 414.1.1
IBC 414.1.2
IBC 414.1.3
Information required Submit a report of maximum hazardous material quantities by class and their protection; Group H also needs floor plans of contents and processes. International Building Code, 2024 · Chapter 4, Special Detailed Requirements Based on Occupancy and Use Read the full text (opens UpCodes in a new tab)
IBC 414.2.1
IBC 414.2.2
Percentage of maximum allowable quantities Per Table 414.2.2: first floor 100% of MAQ with 4 control areas (1-hour), second 75%/3, third 50%/2, fourth–sixth 12.5%/2 (2-hour), above that 5%; basement 1 75%/3, basement 2 50%/2, lower not allowed. International Building Code, 2024 · Chapter 4, Special Detailed Requirements Based on Occupancy and Use Read the full text (opens UpCodes in a new tab)
IBC 414.2.3
IBC 414.2.4
Fire-resistance rating requirements Control area floors and supports are 2-hour, or 1-hour in sprinklered IIA, IIIA, IV and VA up to 3 stories. International Building Code, 2024 · Chapter 4, Special Detailed Requirements Based on Occupancy and Use Read the full text (opens UpCodes in a new tab)
IBC 414.2.5
Hazardous material in Group M display and storage areas and in Group S storage areas Group M and S hazardous materials follow 414.2.5.1 to 414.2.5.4. International Building Code, 2024 · Chapter 4, Special Detailed Requirements Based on Occupancy and Use Read the full text (opens UpCodes in a new tab)
IBC 414.5.1
Explosion control Explosion control (barricade or venting/prevention) per Table 414.5.1 above MAQ or for explosion hazards. Works with IBC 415 IFC
International Building Code, 2024 · Chapter 4, Special Detailed Requirements Based on Occupancy and Use Read the full text (opens UpCodes in a new tab)
IBC 414.5.2
Emergency or standby power Hazmat ventilation, treatment, alarm and detection systems get emergency or standby power where required. Works with IBC 2702
International Building Code, 2024 · Chapter 4, Special Detailed Requirements Based on Occupancy and Use Read the full text (opens UpCodes in a new tab)
IBC 414.5.3
Spill control, drainage and containment Storage of hazardous solids and liquids gets spill control and containment where the IFC requires. Works with IFC
International Building Code, 2024 · Chapter 4, Special Detailed Requirements Based on Occupancy and Use Read the full text (opens UpCodes in a new tab)
IBC 414.6.1
Weather protection Covered outdoor storage stays 'outdoor' if it meets 414.6.1.1 to 414.6.1.3. International Building Code, 2024 · Chapter 4, Special Detailed Requirements Based on Occupancy and Use Read the full text (opens UpCodes in a new tab)
IBC 414.1.2.1
Aerosol products, aerosol cooking spray products and plastic aerosol 3 products Level 2–3 aerosols are stored and displayed per the IFC. Works with IBC 311.2
International Building Code, 2024 · Chapter 4, Special Detailed Requirements Based on Occupancy and Use Read the full text (opens UpCodes in a new tab)
IBC 414.2.5.1
Nonflammable solids and nonflammable and noncombustible liquids M and S may exceed MAQ for nonflammable materials up to Table 414.2.5.1 (e.g. corrosives 9,750 lb/975 gal, toxics 1,000 lb/100 gal) without becoming Group H. International Building Code, 2024 · Chapter 4, Special Detailed Requirements Based on Occupancy and Use Read the full text (opens UpCodes in a new tab)
IBC 414.2.5.2
Flammable and combustible liquids Retail and wholesale may store liquids per Table 414.2.5.2: Class IA 60 gal sprinklered (30 unsprinklered); IB–IIIA 7,500–15,000 sprinklered (1,600 unsprinklered). International Building Code, 2024 · Chapter 4, Special Detailed Requirements Based on Occupancy and Use Read the full text (opens UpCodes in a new tab)
IBC 414.2.5.3
Aerosol products, aerosol cooking spray products or plastic aerosol 3 products Aerosol quantities in Group M follow the IFC. Works with IFC
International Building Code, 2024 · Chapter 4, Special Detailed Requirements Based on Occupancy and Use Read the full text (opens UpCodes in a new tab)
IBC 414.2.5.4
Flammable gas Low-BV Category 1B gas in M or S may reach 390,000 cu ft sprinklered (195,000 unsprinklered) or 40,000/20,000 lb liquefied. International Building Code, 2024 · Chapter 4, Special Detailed Requirements Based on Occupancy and Use Read the full text (opens UpCodes in a new tab)
IBC 414.5.2.1
Exempt applications No standby power needed for ventilation of small closed-container IB/IC liquids, Class 1–2 oxidizers, Class II–V organic peroxides, and asphyxiant gases. International Building Code, 2024 · Chapter 4, Special Detailed Requirements Based on Occupancy and Use Read the full text (opens UpCodes in a new tab)
IBC 414.5.2.2
Fail-safe engineered systems Approved fail-safe systems remove the standby power need. International Building Code, 2024 · Chapter 4, Special Detailed Requirements Based on Occupancy and Use Read the full text (opens UpCodes in a new tab)
IBC 414.6.1.1
IBC 414.6.1.2
IBC 414.6.1.3
IBC 307.2
IBC 309.2
Quantity of hazardous materials Nonflammable hazardous solids and liquids stored or displayed per control area in Group M are limited by Table 414.2.5.1. Works with IBC 414.2.5.1
International Building Code, 2024 · Chapter 3, Occupancy Classification and Use Read the full text (opens UpCodes in a new tab)
IBC 415.2
IBC 421.6
IBC 707.3.8
IBC 415.6.4.4
IBC 415.11.6.5
Searches all 4,276 IRC 2024 sections, 5,532 IBC 2024 sections and defined terms (Chapters 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16, 17, 18, 19, 20, 21, 22, 23, 24, 25, 26, 27, 28, 29, 30, 31, 32, 33 so far) and each city's local rules as they are added. Section numbers and titles from the International Residential Code and International Building Code, 2024 editions, copyrighted by the International Code Council; the IRC's electrical chapters (34 to 43) follow NFPA 70, the National Electrical Code. Requirements are summarized in our words (IRC Chapters 3 to 43, IBC Chapters 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16, 17, 18, 19, 20, 21, 22, 23, 24, 25, 26, 27, 28, 29, 30, 31, 32, 33); read the full text at the link on each result. Local values come from each city's published documents.