Only service conductors go in a service raceway, cable, handhole or underground box, except grounding/bonding conductors and protected load-management control wires (NEC 230.7).
Exposed GECs are fastened; 6 AWG may run unprotected if not exposed to damage, smaller sizes go in RMC, IMC, PVC, RTRC-XW, EMT or armor; bare aluminum stays 18 in above earth (NEC 250.64(A), (B)).
Branch-Circuit Load for Ranges and Cooking Appliances
One range may use the demand table; one wall oven or cooktop uses its nameplate; a cooktop and up to two ovens on one circuit in one room are summed as one range (NEC 220.55 Notes 4-6).
Searches all 4,276 IRC 2024 sections, 5,532 IBC 2024 sections and defined terms (Chapters 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16, 17, 18, 19, 20, 21, 22, 23, 24, 25, 26, 27, 28, 29, 30, 31, 32, 33 so far) and each city's local rules as they are added. Section numbers and titles from the International Residential Code and International Building Code, 2024 editions, copyrighted by the International Code Council; the IRC's electrical chapters (34 to 43) follow NFPA 70, the National Electrical Code. Requirements are summarized in our words (IRC Chapters 3 to 43, IBC Chapters 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16, 17, 18, 19, 20, 21, 22, 23, 24, 25, 26, 27, 28, 29, 30, 31, 32, 33); read the full text at the link on each result. Local values come from each city's published documents.