  • E3702.9

    Branch-Circuit Inductive and LED Lighting Loads

    • Ballasted and LED-driver lighting loads use the units' ampere ratings, not lamp watts (NEC 220.11(B)).

    International Residential Code, 2024 · Chapter 37, Branch Circuit and Feeder RequirementsRead the full text (opens UpCodes in a new tab)

  • E3901.7

    Outdoor Outlets

    • Front and back of each dwelling with grade access get an outdoor receptacle reachable from grade, no more than 6 ft 6 in up; decks, porches and balconies get one within 6 ft 6 in of the surface (NEC 210.52(E)).

    International Residential Code, 2024 · Chapter 39, Power and Lighting DistributionRead the full text (opens UpCodes in a new tab)

  • E3902.21

    Arc-Fault Circuit Interrupter Protection

    • 120 V, 10-20 A outlets in kitchens, living, family, dining, bedrooms, closets, halls, laundry and similar areas get AFCI protection by a combination breaker or one of the allowed outlet-AFCI arrangements (home run 50 ft for 14 AWG, 70 ft for 12 AWG) (NEC 210.12(A)).

    International Residential Code, 2024 · Chapter 39, Power and Lighting DistributionRead the full text (opens UpCodes in a new tab)

  • E3908.21

    Installation Equipment Bonding Jumper

    • Bonding jumpers run inside or outside raceways per E3908.21.1 and E3908.21.2 (NEC 250.102(E)).

    International Residential Code, 2024 · Chapter 39, Power and Lighting DistributionRead the full text (opens UpCodes in a new tab)

Searches all 4,276 IRC 2024 sections, 5,532 IBC 2024 sections and defined terms (Chapters 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16, 17, 18, 19, 20, 21, 22, 23, 24, 25, 26, 27, 28, 29, 30, 31, 32, 33 so far) and each city's local rules as they are added. Section numbers and titles from the International Residential Code and International Building Code, 2024 editions, copyrighted by the International Code Council; the IRC's electrical chapters (34 to 43) follow NFPA 70, the National Electrical Code. Requirements are summarized in our words (IRC Chapters 3 to 43, IBC Chapters 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16, 17, 18, 19, 20, 21, 22, 23, 24, 25, 26, 27, 28, 29, 30, 31, 32, 33); read the full text at the link on each result. Local values come from each city's published documents.