Vapor retarders are Class I (0.1 perm or less, like poly), Class II (0.1-1.0, kraft or VR paint) or Class III (1.0-10, latex paint).
Zones 1-2 allow only Class III vapor retarders (none is required); zones 3-4 allow II or III; colder zones allow I, II, or III with the right cladding or exterior insulation.
Where exterior foam lets you use a lighter retarder, the needed R-value rises with climate zone and wall depth (e.g. zone 5: R-5 over 2x4, R-7.5 over 2x6 for Class III).
Local review: San Antonio is climate zone 2A: don't put poly or other Class I/II vapor retarders on the inside of exterior walls.
Roof panels are graded and marked, exterior-rated if permanently exposed (Exposure 1 is fine underneath), span per the panel table, and overhang gable ends no more than 9 in without framing.
Searches all 4,276 IRC 2024 sections, 5,532 IBC 2024 sections and defined terms (Chapters 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16, 17, 18, 19, 20, 21, 22, 23, 24, 25, 26, 27, 28, 29, 30, 31, 32, 33 so far) and each city's local rules as they are added. Section numbers and titles from the International Residential Code and International Building Code, 2024 editions, copyrighted by the International Code Council; the IRC's electrical chapters (34 to 43) follow NFPA 70, the National Electrical Code. Requirements are summarized in our words (IRC Chapters 3 to 43, IBC Chapters 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16, 17, 18, 19, 20, 21, 22, 23, 24, 25, 26, 27, 28, 29, 30, 31, 32, 33); read the full text at the link on each result. Local values come from each city's published documents.
Check your plans against these codes
Start an application and get every flag with its section and fix.