Tile follows the ANSI A108/A118/A136/A137 standards, and tub and shower walls use glass-mat gypsum, fiber-reinforced gypsum, fiber-cement or cement board backers.
Unvented Attic and Unvented Enclosed Rafter Assemblies
Unvented attics are allowed inside the thermal envelope with no Class I retarder on the ceiling, using spray foam against the deck, rigid foam above it, or a combination meeting the condensation R-value.
Condensation-control insulation for unvented attics is R-5 in zones 1-3 (none for tile roofs in 2B/3B), rising to R-10 (4C), R-15 (4A/B), R-20, R-25, R-30 and R-35 in zones 5-8.
In zones 1-3, unvented attics with fluffy insulation can use a vapor diffusion port near the ridge (1/600 of ceiling area, 20+ perms) on a 3:12 or steeper roof, with supply air of 50 cfm per 1,000 sq ft if insulation is at the deck.
Local review: San Antonio (2A) unvented attics need at least R-5 of spray foam or rigid board at the roof deck, or a vapor diffusion port setup.
Cripple walls are braced like the wall above, with 15% more length; in SDC D0/D1 and SDC C townhouses only panel methods, with panels no more than 14 ft apart.
Cripple walls 48 in or shorter can count as the first story; if any part is taller, the cripple wall is an extra story.
Searches all 4,276 IRC 2024 sections, 5,532 IBC 2024 sections and defined terms (Chapters 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16, 17, 18, 19, 20, 21, 22, 23, 24, 25, 26, 27, 28, 29, 30, 31, 32, 33 so far) and each city's local rules as they are added. Section numbers and titles from the International Residential Code and International Building Code, 2024 editions, copyrighted by the International Code Council; the IRC's electrical chapters (34 to 43) follow NFPA 70, the National Electrical Code. Requirements are summarized in our words (IRC Chapters 3 to 43, IBC Chapters 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16, 17, 18, 19, 20, 21, 22, 23, 24, 25, 26, 27, 28, 29, 30, 31, 32, 33); read the full text at the link on each result. Local values come from each city's published documents.