Veneer ties are corrugated 22-gauge strip or 9-gauge wire, embedded 1-1/2 in with 5/8 in cover, each covering 2.67 sq ft at 32 in across and 24 in up, with a 1 in airspace.
Openings over 16 in get extra ties within 12 in, spaced 3 ft or less around the edge.
Steel joists get bearing stiffeners at every bearing (except lapped joists with no wall above), sized to the wall stud above, at least the joist depth less 3/8 in long.
Searches all 4,276 IRC 2024 sections, 5,532 IBC 2024 sections and defined terms (Chapters 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16, 17, 18, 19, 20, 21, 22, 23, 24, 25, 26, 27, 28, 29, 30, 31, 32, 33 so far) and each city's local rules as they are added. Section numbers and titles from the International Residential Code and International Building Code, 2024 editions, copyrighted by the International Code Council; the IRC's electrical chapters (34 to 43) follow NFPA 70, the National Electrical Code. Requirements are summarized in our words (IRC Chapters 3 to 43, IBC Chapters 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16, 17, 18, 19, 20, 21, 22, 23, 24, 25, 26, 27, 28, 29, 30, 31, 32, 33); read the full text at the link on each result. Local values come from each city's published documents.