Steel joists get bearing stiffeners at every bearing (except lapped joists with no wall above), sized to the wall stud above, at least the joist depth less 3/8 in long.
Ledger lag screws and bolts are 1/2 in, spaced per the table by joist span and load, with lag holes drilled 1/2 in through the ledger and 5/16 to 3/8 in into the band.
Ledger fasteners stay 2 in from the ledger top and ends and 3/4 in from its bottom, staggered, with rows 1-5/8 to 5 in apart; in the band, 3/4 in from top and 2 in from bottom.
Sill plates and exterior sole plates on slabs are anchored with 1/2 in bolts at 6 ft or less, embedded 7 in, in the middle third of the plate, with a nut and washer.
Each plate piece gets at least two bolts, with one within 12 in of each end but no closer than seven bolt diameters.
Short offset walls between braced panels need one bolt if 24 in or shorter, and none if 12 in or shorter, when tied to the panels at the corners.
Searches all 4,276 IRC 2024 sections, 5,532 IBC 2024 sections and defined terms (Chapters 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16, 17, 18, 19, 20, 21, 22, 23, 24, 25, 26, 27, 28, 29, 30, 31, 32, 33 so far) and each city's local rules as they are added. Section numbers and titles from the International Residential Code and International Building Code, 2024 editions, copyrighted by the International Code Council; the IRC's electrical chapters (34 to 43) follow NFPA 70, the National Electrical Code. Requirements are summarized in our words (IRC Chapters 3 to 43, IBC Chapters 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16, 17, 18, 19, 20, 21, 22, 23, 24, 25, 26, 27, 28, 29, 30, 31, 32, 33); read the full text at the link on each result. Local values come from each city's published documents.
Check your plans against these codes
Start an application and get every flag with its section and fix.