In SDC D, plain concrete walls are at most 8 ft tall with 4 ft of backfill and at least 7.5 in thick (6 in if 4 ft 6 in tall or less); walls the tables allow plain still get No. 4 bars at 48 in.
Prescriptive wind rules stop applying where the map requires wind design, or at 140 mph or more in a special wind region; the house is then designed to WFCM, ICC 600, ASCE 7, AISI S230 or the IBC.
Shingle, tile, metal, slate, wood and solar roofs get labelled underlayment; in normal-wind areas felt, synthetic or self-adhered types qualify, while wind-design areas need the heavier types.
Under shingles, 2:12 to 4:12 roofs get two layers (a half-sheet starter, then sheets lapped half plus 2 in); 4:12 and steeper get one layer lapped 2 in; end laps are 4 in, staggered 6 ft.
In wind-design areas, use two fastened layers, 4 in self-adhered strips over deck joints plus underlayment, or full self-adhered; cap nails go in a 12 in grid with 6 in at laps.
Searches all 4,276 IRC 2024 sections, 5,532 IBC 2024 sections and defined terms (Chapters 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16, 17, 18, 19, 20, 21, 22, 23, 24, 25, 26, 27, 28, 29, 30, 31, 32, 33 so far) and each city's local rules as they are added. Section numbers and titles from the International Residential Code and International Building Code, 2024 editions, copyrighted by the International Code Council; the IRC's electrical chapters (34 to 43) follow NFPA 70, the National Electrical Code. Requirements are summarized in our words (IRC Chapters 3 to 43, IBC Chapters 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16, 17, 18, 19, 20, 21, 22, 23, 24, 25, 26, 27, 28, 29, 30, 31, 32, 33); read the full text at the link on each result. Local values come from each city's published documents.
Check your plans against these codes
Start an application and get every flag with its section and fix.