Steel outlet boxes up to 16 sq in may pierce a rated wall's membrane if they total no more than 100 sq in per 100 sq ft, gaps are 1/8 in or less, and opposite boxes are 24 in apart or otherwise protected.
Plaster thickness depends on the base: 5/8 in over metal lath, 1/2 in over gypsum lath or masonry for gypsum plaster; cement plaster 3/4 in interior and 7/8 in exterior over wire lath or sheathing.
Wall rebar is A615, A706 or A996M; anchor bolts are headed A307 Grade A or F1554 Grade 36 (or threaded A36 rod with a nut), with no J- or L-bolts in the connection details.
Searches all 4,276 IRC 2024 sections, 5,532 IBC 2024 sections and defined terms (Chapters 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16, 17, 18, 19, 20, 21, 22, 23, 24, 25, 26, 27, 28, 29, 30, 31, 32, 33 so far) and each city's local rules as they are added. Section numbers and titles from the International Residential Code and International Building Code, 2024 editions, copyrighted by the International Code Council; the IRC's electrical chapters (34 to 43) follow NFPA 70, the National Electrical Code. Requirements are summarized in our words (IRC Chapters 3 to 43, IBC Chapters 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16, 17, 18, 19, 20, 21, 22, 23, 24, 25, 26, 27, 28, 29, 30, 31, 32, 33); read the full text at the link on each result. Local values come from each city's published documents.