Per Table 414.2.2: first floor 100% of MAQ with 4 control areas (1-hour), second 75%/3, third 50%/2, fourth–sixth 12.5%/2 (2-hour), above that 5%; basement 1 75%/3, basement 2 50%/2, lower not allowed.
Nonflammable solids and nonflammable and noncombustible liquids
M and S may exceed MAQ for nonflammable materials up to Table 414.2.5.1 (e.g. corrosives 9,750 lb/975 gal, toxics 1,000 lb/100 gal) without becoming Group H.
Retail and wholesale may store liquids per Table 414.2.5.2: Class IA 60 gal sprinklered (30 unsprinklered); IB–IIIA 7,500–15,000 sprinklered (1,600 unsprinklered).
Searches all 4,276 IRC 2024 sections, 5,532 IBC 2024 sections and defined terms (Chapters 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16, 17, 18, 19, 20, 21, 22, 23, 24, 25, 26, 27, 28, 29, 30, 31, 32, 33 so far) and each city's local rules as they are added. Section numbers and titles from the International Residential Code and International Building Code, 2024 editions, copyrighted by the International Code Council; the IRC's electrical chapters (34 to 43) follow NFPA 70, the National Electrical Code. Requirements are summarized in our words (IRC Chapters 3 to 43, IBC Chapters 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16, 17, 18, 19, 20, 21, 22, 23, 24, 25, 26, 27, 28, 29, 30, 31, 32, 33); read the full text at the link on each result. Local values come from each city's published documents.