The open space must be at least 20 ft wide, measured from the building to the nearest interior lot line, across the full street, or to another building on the lot; use the narrowest qualifying width.
Frontage increase If from Table 506.3.3: by % of perimeter (25–50, 50–75, 75–100) and open space width (20–25, 25–30, 30+ ft): 0.17/0.21/0.25, 0.33/0.42/0.50, 0.50/0.63/0.75; interpolation allowed.
Allowable area comes from 506.2.1, 506.2.2 and the frontage increase in 506.3, using Table 506.2 factors.
Unsprinklered (NS) factors, e.g. VB: B 9,000, M 9,000, A-2/A-3 6,000, E 9,500, R-1/R-2/R-4 7,000, S-1 9,000, U 5,500; R-3 is unlimited. For these groups the sprinklered one-story factor (S1) is 4 × NS and multistory (SM) is 3 × NS.
Searches all 4,276 IRC 2024 sections, 5,532 IBC 2024 sections and defined terms (Chapters 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16, 17, 18, 19, 20, 21, 22, 23, 24, 25, 26, 27, 28, 29, 30, 31, 32, 33 so far) and each city's local rules as they are added. Section numbers and titles from the International Residential Code and International Building Code, 2024 editions, copyrighted by the International Code Council; the IRC's electrical chapters (34 to 43) follow NFPA 70, the National Electrical Code. Requirements are summarized in our words (IRC Chapters 3 to 43, IBC Chapters 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16, 17, 18, 19, 20, 21, 22, 23, 24, 25, 26, 27, 28, 29, 30, 31, 32, 33); read the full text at the link on each result. Local values come from each city's published documents.